14.7kW at 3000 RPM Lister Petter Diesel Fire Engine- Radiator Cooled

Model No.: LPW2-46R-13

Lister Petter diesel air radiator cooled diesel engines fully comply with the strict Australian fire engine standards AS 2941-2013. With Lister’s legendary performance and reliability these engines are perfect for both industrial and commercial fire fighting systems. They pair perfectly with our Diesel Fire Pump Controller.

Power Rating: 14.7 kW
Engine Model: LISTER PETTER
engine speed: 3000 rpm
Starter Voltage: 12 V
Cylinder No.: 2
Cubic Capacity: 0.93Lt
max. speed: 3000 rpm
Flywheel Housing: SAE #5
Flywheel: 7.5-40mm Stub Shaft
Combustion Air Flow: 19.75 L/Sec
Heat Rejection to Coolant: 14 kW
Heat Rejection to Atmosphere: 5 kW
Radiator Fan Air Flow: 2.03 L/sec
Exhaust Gas Flow: 55.2 L/Sec
Exhaust Gas Temperature: 520 °C
Exhaust Pipe Size: 2″”
Governing: Mechanical
Approx. Fuel Consumption @ Full Load: 3 hrs

*Specifications are subject to change without notice
  • Air radiator cooling
  • Engine feet
  • Energise to stop solenoid fitted
  • Speed transducer fitted
  • Condensation trap below exhaust manifold
  • Guards fitted to suit 2013 specifications
  • Exhaust flex muffler (supplied loose)
  • Jacket heater with additional dry contact for remote indicator (if applicable)
  • fuel lines to suit 2013 specifications
  • oil pressure sender fitted
  • Engine water temp sender fitted

** This engine fully complies with the Australian Standard AS2941-2013

Firepump Ratings Spreadsheet

Technical Drawing