240kVA, 3 Phase, Diesel Standby Generator with Doosan Engine in Canopy

Model No.: ED240DSE/3C

The Doosan powered ED240DSE/3C is a 240kVA three phase diesel generator. Complete with Crossley SLG series single bearing, 4-pole, brushless alternator, remote start/stop control system and 500 litre fuel tank. Welling and Crossley’s Doosan powered generators are fully integrated power generation systems that are stringently tested to provide optimum performance, reliability, and versatility for both stationary and prime power applications. Weather protective acoustic canopy included.

Alternator

Alternator Model: Crossley SLG Series
Electric Power: Three Phase
Active Rating: 240 kVA at 0.8 pf (Standby)
Power: 192 kW
Electric Potential: 415V
Frequency: 50Hz

Engine

Engine Model: Doosan P086Ti
Engine Speed: 1500 rpm
Cylinder No.: 6Ti
Cubic Capacity: 8.071 L
Bore / Stroke: 111 x 139 mm
Compression Ratio: 16.4 : 1
Aspiration: Turbocharged, Aftercooled
Starter Voltage: 24V
Flywheel ( Max. Continuous Power): 242 kW
Combustion Air Flow: 18.4 m³/min
Cooling Air Flow: 359 m³/min
Cooling System: Radiator Cooled
Heat Rejection to Cooling System: 200 kW
Exhaust Gas Flow: 30 m³/min
Exhaust Gas Temperature: 583°C
Fuel Type: Diesel
Fuel Tank Capacity: 400 L
Approx. Fuel Consumption (Continuous): N/A
Approx. Fuel Consumption (Standby): 62.4 L/hr

Generator

Dimensions (L x W x H): 3800 x 1300 x 2050 mm (L x W x H)
Weight: 4100 kg

*Specifications are subject to change without notice

The control starting system is fitted standard. Starting is remote or local to the machine with push Start/Stop button and includes the following digital indicators:

  • Oil Pressure
  • Engine Temperature
  • Frequency
  • Volts and Amps
  • Shut Down for low oil & temperature
  • Emergency stop button
  • Output circuit breaker
  • Static Battery Charger

Can also be configured to operate with an Automatic Transfer Switch with logic.

  • Heavy duty fabricated steel baseframe

The complete generating set is mounted as a whole onto a heavy duty fabricated steel baseframe. Anti-vibration pads are fixed between the engine and alternator feet, and the baseframe, ensuring complete vibration isolation of the rotating assembly.

  • Bunded Fuel Tank (AS 1940-2004 compliant)

The fuel tank is fully bunded and complies fully with relevant sections in AS 1940-2004. It has a secondary containment compound with a capacity as big or bigger than that of the tank, and is made of surface coated steel. This compound is designed to sufficiantly retain spillage and enable recovery of any spillage. For more information regarding AS 1940-2004 compliance refer to the standard, or contact us.

  • Battery Charger

This trickle charge battery charger ensures that your generator can start up when needed. It has both 12v and 24v charging capabilities.

  • Control Panel with Emergency Stop button

This control panel monitors the controls of a single unit to achieve automatic start/stop, data measuring/monitoring, alarm protection and three remote systems (remote control, remote measuring and remote communication). The controller adopts large liquid crystal display (LCD) and has a 32 bit micro-processor with precision parameters for measuring, fixed value adjustment, time setting and threshold adjustment.

  • Prime or Standby Power

Standby: kVA @ 0.8 pf These ratings are applicable for supplying continuous electrical power (at variable loads) in the event of a utility power failure. No overload is permitted on these ratings. Minimum output from alternators are peak continuous rated (as defined in 1SO 8528-3 @ 27°C. Annual hour limitation: 500 hours).

Prime (continuous): kVA @ 0.8 pf. (Divide standby rating by 1.1). Available for continuous electrical output. There is no hour limitation. 10% overload is available 1 hour in 12. The generating set and this specification is designed for environmental conditions of up to 27°C, up to 152.4 m above sea level and up to 60% relative humidity. Ratings at 0.8 pf.
For ratings outside this range, please contact us.

  • Canopy Option (Standard Build)
    A weather protective acoustic enclosure is fitted to protect and prolong the life of your generator. Constructed of galvanised steel sheet that is cleared and finished using a powdercoat paint finish, this acoustic canopy will reduce the noise level of the generating set to approximately 80 dB(A) at 1 metre from the machine (73 dB(A) @ 7 m).Requires 900 mm access (width) to open doors, and the exhaust
    protrudes 300 mm above the canopy.
    Dimensions: 3800 mm (L) x 1300 mm (W) x 2050 mm (H)
  • Additional Protection Alarms
  • Jacket Heater
  • Automatic Transfer Switch (ATS)
  • Control System (remote Start/Stop) with Mains Failure option
  • Weather protected acoustic canopy
  • Trailer mounted
  • Load Banks
  • Auxiliary Fuel Tanks
  • Genuine Spare Parts